summaryrefslogtreecommitdiffstats
path: root/requirements/07-annex.rst
diff options
context:
space:
mode:
Diffstat (limited to 'requirements/07-annex.rst')
-rw-r--r--requirements/07-annex.rst64
1 files changed, 64 insertions, 0 deletions
diff --git a/requirements/07-annex.rst b/requirements/07-annex.rst
new file mode 100644
index 00000000..dbe41bd1
--- /dev/null
+++ b/requirements/07-annex.rst
@@ -0,0 +1,64 @@
+Annex: NFVI Faults
+=================================================
+
+Faults in the listed elements need to be immediately notified to the Consumer in
+order to perform an immediate action like live migration or switch to a hot
+standby entity. In addition, the Administrator of the host should trigger a
+maintenance action to, e.g., reboot the server or replace a defective hardware
+element.
+
+Faults can be of different severity, i.e., critical, warning, or
+info. Critical faults require immediate action as a severe degradation of the
+system has happened or is expected. Warnings indicate that the system
+performance is going down: related actions include closer (e.g. more frequent)
+monitoring of that part of the system or preparation for a cold migration to a
+backup VM. Info messages do not require any action. We also consider a type
+"maintenance", which is no real fault, but may trigger maintenance actions
+like a re-boot of the server or replacement of a faulty, but redundant HW.
+
+Faults can be gathered by, e.g., enabling SNMP and installing some open source
+tools to catch and poll SNMP. When using for example Zabbix one can also put an
+agent running on the hosts to catch any other fault. In any case of failure, the
+Administrator should be notified. The following table provides a list of high
+level faults that are considered within the scope of the Doctor project
+requiring immediate action by the Consumer.
+
+
+
++------------------+---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| Service | Fault | Severity | How to detect? | Comment | Action to recover |
++------------------+---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| Compute Hardware | Processor/CPU failure, CPU condition not ok | Critical | Zabbix | | Switch to hot standby |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | Memory failure/Memory condition not ok | Critical | Zabbix (IPMI) | | Switch to hot standby |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | Network card failure, e.g. network adapter connectivity lost | Critical | Zabbix/Ceilometer | | Switch to hot standby |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | Disk crash | Info | RAID monitoring | Network storage is very redundant (e.g. RAID system) and can guarantee high availability | Inform OAM |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | Storage controller | Critical | Zabbix (IPMI) | | Live migration if storage is still accessible; otherwise hot standby |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | PDU/power failure, power off, server reset | Critical | Zabbix/Ceilometer | | Switch to hot standby |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | Power degradation, power redundancy lost, power threshold exceeded | Warning | SNMP | | Live migration |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | Chassis problem (.e.g fan degraded/failed, chassis power degraded), CPU fan problem, temperature/thermal condition not ok | Warning | SNMP | | Live migration |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | Mainboard failure | Critical | Zabbix (IPMI) | | Switch to hot standby |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | OS crash (e.g. kernel panic) | Critical | Zabbix | | Switch to hot standby |
++------------------+---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| Hypervisor | System has restarted | Critical | Zabbix | | Switch to hot standby |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | Hypervisor failure | Warning/Critical | Zabbix/Ceilometer | | Evacuation/switch to hot standby |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | Zabbix/Ceilometer is unreachable | Warning | ? | | Live migration |
++------------------+---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| Network | SDN/OpenFlow switch, controller degraded/failed | Critical | ? | | Switch to hot standby or reconfigure virtual network topology |
++ +---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+| | Hardware failure of physical switch/router | Warning | SNMP | Redundancy of physical infrastructure is reduced or no longer available | Live migration if possible, otherwise evacuation |
++------------------+---------------------------------------------------------------------------------------------------------------------------+------------------+-------------------+------------------------------------------------------------------------------------------+----------------------------------------------------------------------+
+
+..
+ vim: set tabstop=4 expandtab textwidth=80:
+